dc.identifier.citationKotcioğlu, İ., Çalışkan, S., Başkaya, Ş. (2011). Experimental study on the heat transfer and pressure drop of a cross-flow heat exchanger with different pin–fin arrays. Heat and Mass Transfer, 47(9), 1133-1142.en_US
dc.identifier.issn0947-7411
dc.identifier.urihttps://doi.org/10.1007/s00231-011-0779-7
dc.identifier.urihttps://hdl.handle.net/11491/1102
dc.description.abstractIn this study, convective heat transfer and pressure drop in a cross-flow heat exchanger with hexagonal, square and circular (HSC) pin-fin arrays were studied experimentally. The pin-fins were arranged in an in-line manner. For the applied conditions, the optimal spacing of the pin-fin in the span-wise and stream-wise directions has been determined. The variable parameters are the relative longitudinal pitch (SL /D = 2, 2.8, 3.5), and the relative transverse pitch was kept constant at ST /D = 2. The performances of all pin-fins were compared with each other. The experimental results showed that the use of hexagonal pin-fins, compared to the square and circular pin-fins, can lead to an advantage in terms of heat transfer enhancement. The optimal inter-fin pitches are provided based on the largest Nusselt number under the same pumping power, while the optimal inter-fin pitches of hexagonal pin-fins are ST /D = 2 and SL /D = 2.8. Empirical equations are derived to correlate the mean Nusselt number and friction coefficient as a function of the Reynolds number, pin-fin frontal surface area, total surface area, and total number. Consequently, the general empirical formula is given in the present form. NuD = a(ReD)b(N tAf/Atotal)c and f = a(Re D)b © 2011 Springer-Verlag.en_US
dc.language.isoeng
dc.relation.isversionof10.1007/s00231-011-0779-7en_US
dc.rightsinfo:eu-repo/semantics/closedAccessen_US
dc.subjectHeat Transferen_US
dc.subjectRoot Mean Square Erroren_US
dc.subjectNusselt Numberen_US
dc.subjectTest Sectionen_US
dc.subjectFriction Factoren_US
dc.titleExperimental study on the heat transfer and pressure drop of a cross-flow heat exchanger with different pin-fin arraysen_US
dc.typearticleen_US
dc.relation.journalHeat and Mass Transfer/Waerme- und Stoffuebertragungen_US
dc.departmentHitit Üniversitesi, Mühendislik Fakültesi, Makine Mühendisliği Bölümüen_US
dc.authorid0000-0002-7753-0355en_US
dc.identifier.volume47en_US
dc.identifier.issue9en_US
dc.identifier.startpage1133en_US
dc.identifier.endpage1142en_US
dc.relation.publicationcategoryMakale - Uluslararası Hakemli Dergi - Kurum Öğretim Elemanıen_US


Bu öğenin dosyaları:

DosyalarBoyutBiçimGöster

Bu öğe ile ilişkili dosya yok.

Bu öğe aşağıdaki koleksiyon(lar)da görünmektedir.

Basit öğe kaydını göster