dc.contributor.advisorKılıçarslan, Ali
dc.contributor.authorKalender, Tufan
dc.date.accessioned2021-11-01T14:48:05Z
dc.date.available2021-11-01T14:48:05Z
dc.date.issued2021
dc.identifier.citationKalender, Tufan. (2021). Farklı Rankine çevrimlerinin termodinamik açıdan incelenmesi. (Yayınlanmamış Yüksek Lisans Tezi). Hitit Üniversitesi, Lisansüstü Eğitim Enstitüsü, Makine Mühendisliği Anabilim Dalıen_US
dc.identifier.urihttps://tez.yok.gov.tr/UlusalTezMerkezi/TezGoster?key=v7BkNnnepTnbhn8rNR77LRIVDhy_7uzaFxzW4DTFhXSlMRQhzC2OjF0czbw8QwXj
dc.identifier.urihttps://hdl.handle.net/11491/6019
dc.descriptionYÖK ID: 682493en_US
dc.description.abstractTez çalışmasında, literatürdeki çalışmalardan farklı olarak, 4 kademe genişlemeli, 2 açık besleme suyu ısıtıcılı, 1 kapalı besleme suyu ısıtıcılı, ara ısıtmalı ve ara ısıtmasız Rankine çevrimleri modellenmiş ve çevrimler termodinamiğin I. ve II. kanunlarına göre analiz edilmiştir. EES (Engineering Equation Solver) yazılımı kullanılarak, Rankine çevrimleri için bilgisayar programı geliştirilmiş, 500? ile 620? arasındaki türbin 1 giriş sıcaklıklarına ve 18000 kPa ile 30000 kPa arasındaki türbin 1 basınçlarına göre, kazana verilmesi gereken ısı miktarı, türbinlerin ürettiği toplam güç, pompaların tükettiği toplam güç, çevrimin ürettiği toplam güç, yoğuşturucunun çevreye verdiği ısı miktarı, çevrimin birinci ve ikinci kanun verimleri, açık besleme suyu ısıtıcılarının ve kapalı besleme suyu ısıtıcısının ikinci kanun verimleri incelenmiştir. Türbin 1 giriş sıcaklığı arttırıldığında, ara ısıtmalı çevrimde, elde edilen maksimum gücün, ara ısıtmasız çevrimde elde edilen maksimum güce göre 1,22 kat daha fazla olduğu tespit edilmiştir. Maksimum birinci kanun verimlerinin (ısıl verimlerin) ara ısıtmalı ve ara ısıtmasız çevrimlerde, sırasıyla % 42,21 ve % 41,11 olduğu belirlenmiştir. Maksimum ikinci kanun verimleri dikkate alındığında, ara ısıtmalı çevrimde % 91,46 ve ara ısıtmasız çevrimde % 71,28 değerleri elde edilmiştir. Her iki durumda da pompaların tükettiği toplam güç değerinde ve açık besleme suyu ısıtıcısı 2'in (ABSI2) ikinci kanun veriminde ihmal edilecek kadar değişiklik olduğu tespit edilmiştir. Türbin 1 giriş basıncı arttırıldığında, ara ısıtmalı çevrimde üretilen güç 52459 kW, ara ısıtmasız çevrimde ise 43523 kW olmuştur. Her iki çevrimde üretilen güçlerin oransal değeri 1,2'dir. Termodinamiğin I. kanununa göre hesaplananan verimler, ara ısıtmalı ve ara ısıtmasız durumlar çin birbirine çok yakın % 40 civarındadır. Çevrimin ikinci kanun veriminin, ara ısıtmalı durumda ortalama % 90, ara ısıtmasız durumda ise ortalama % 70,5 olduğu tespit edilmiştir. Pompaların tükettiği toplam güç, ara ısıtmalı ve ara ısıtmasız durumda aynı aralıkta olmuştur ve artan basınç durumlarında % 76 oranında artmıştır. Ara ısıtmasız durumda ABSI2'nin ikinci kanun veriminde artış % 75, ara ısıtmalı durumda ise % 5,83 olarak gerçekleşmiştir.en_US
dc.description.abstractIn the thesis, unlike the studies in the literature, Rankine cycles with 4 stage expansion, 2 open feed water heaters, 1 closed feed water heater, with and without reheating are modeled and analyzed according to the first and secon laws of thermodynamics. A computer program for the Rankine cycles was developed using EES (Engineering Equation Solver) software. The amount of heat supplied to the boiler, the total power produced by the turbines, the total power consumed by the pumps, the total power produced by the cycle, the amount of heat rejected by the condenser to the environment, first and second law efficiencies of the cycles, second law efficiencies of open feedwater heaters and closed feedwater heaters were investigated according to turbine 1 inlet temperatures between 500? and 620? and turbine 1 pressures between 18000 kPa and 30000 kPa. As the turbine 1 inlet temperature is increased, the maximum power obtained in the reheat cycle was found to be 1.22 times higher than the maximum power obtained in the unheated cycle. The maximum first law efficiencies (thermal efficiencies) were determined to be 42.21% and 41.11% in the cycles with and without reheating, respectively. Considering the maximum second law efficiencies, 91,46% in the reheated cycle and 71.28% in the unheated cycle were obtained. In both cases, it has been determined that there is a negligible change in the total power consumed by the pumps and the second law efficiency of the open feedwater heater 2 (OFH2). As the turbine 1 inlet pressure is increased, the power produced in the reheated cycle and the unheated cycle are 52459 kW and 43523 kW, respectively. The proportional value of the powers produced in both cycles is 1.2. The efficiencies calculated according to the first law of thermodynamics are very close to each other, around 40% for the cases with and without reheating. It has been determined that the second law efficiency of the cycle is 90% on average in the case with reheat and 70.5% on average in the case without reheating. The total power consumed by the pumps was in the same range with and without reheat and increased by 76% under increasing pressure conditions. The increase in the second law efficiency of OFH2 in the unheated condition was 75%, and in the reheated condition it was 5.83%.en_US
dc.description.tableofcontentsİÇİNDEKİLER ÖZET -- iv ABSTRACT -- vi TEŞEKKÜR -- viii İÇİNDEKİLER -- ix ŞEKİLLER DİZİNİ -- x SİMGELER VE KISALTMALAR -- xii 1. GİRİŞ -- 1 2. ARA ISITMASIZ RANKİNE ÇEVRİMİNİN TERMODİNAMİK ANALİZİ -- 8 2.1. Ara Rankine Çevriminde Kullanılacak Denge Denklemleri -- 8 2.1.1. Kütlenin korunumu denklemi -- 8 2.1.2. Enerjinin korunumu denklemi -- 8 2.1.3. Entropi Dengesi Denklemi -- 9 2.1.4. Ekserji Dengesi Denklemi -- 9 2.2. Denge Denklemlerinin Çevrim Elemanlarına Uygulanması -- 13 3. ARA ISITMALI RANKİNE ÇEVRİMİNİN TERMODİNAMİK ANALİZİ -- 23 3.1. Denge Denklemlerinin Ara Isıtmalı Rankine Çevrimi Modeline Uygulanması 26 4. ARA ISITMASIZ VE ARA ISITMALI RANKINE ÇEVRIMLERİNİN TERMODINAMIK ANALIZ SONUÇLARI -- 28 5. SONUÇLAR VE ÖNERİLER -- 50 KAYNAKLAR -- 54 ÖZGEÇMİŞ -- 56en_US
dc.language.isoturen_US
dc.publisherHitit Üniversitesien_US
dc.rightsinfo:eu-repo/semantics/openAccessen_US
dc.subjectGüç Çevrimlerien_US
dc.subjectRankine Çevrimien_US
dc.subjectBuhar Türbinlerien_US
dc.subjectIsıl Verimen_US
dc.subjectEkserji Verimien_US
dc.subjectPower Cyclesen_US
dc.subjectRankine Cycleen_US
dc.subjectSteam Turbinesen_US
dc.subjectThermal Efficiencyen_US
dc.subjectExergy Efficiencyen_US
dc.titleFarklı Rankine çevrimlerinin termodinamik açıdan incelenmesien_US
dc.title.alternativeInvestigation of different steam Rankie cycles from thermodynamic point of viewen_US
dc.typemasterThesisen_US
dc.departmentHitit Üniversitesi, Lisansüstü Eğitim Enstitüsü, Makine Mühendisliği Anabilim Dalıen_US
dc.identifier.startpage1en_US
dc.identifier.endpage70en_US
dc.relation.publicationcategoryTezen_US
dc.contributor.institutionauthorKalender, Tufan