Energy and irreversibility analysis of a cascade refrigeration system for various refrigerant couples
Künye
Kılıçarslan, A., Hoşöz, M. (2010). Energy and irreversibility analysis of a cascade refrigeration system for various refrigerant couples. Energy Conversion and Management, 51(12), 2947-2954.Özet
This study deals with energy and irreversibility analysis of a cascade refrigeration system employing various refrigerant couples, namely R152a–R23, R290–R23, R507–R23, R234a–R23, R717–R23 and R404a–R23, using a computer code developed for this aim. It is assumed that the refrigeration load is 1 kW, the refrigerated space temperature is −40 °C, and the environment temperature is 300 K, while the degrees of condenser subcooling and evaporator superheat are 5 and 7 °C, respectively, for all cases. Furthermore, the polytropic efficiencies of the compressors are assumed to be equal. It has been determined that the COP of the cascade refrigeration system increases and the irreversibility decreases with rising evaporator temperature and polytropic efficiency for all studied refrigerant couples. On the other hand, the COP of the cascade refrigeration system decreases and the irreversibility increases on increasing the condenser temperature and the difference between the saturation temperatures of the lower and higher temperature systems in the heat exchanger (ΔT). In all cases, the refrigerant couple R717–R23 has the highest COP and lowest irreversibility except for the limited ranges of polytropic efficiency (50–60%) and ΔT (13 K–16 K), while R507–R23 has the lowest COP and highest irreversibility. The refrigerant couple R152a–R23 has been found to be an alternative couple to R717–R23 for the above mentioned ranges of polytropic efficiency and ΔT. The refrigerant couples R134a–R23 and R290–R23 have placed in the middle range, and R404a–R23 can be considered as a replacement couple for R507–R23 in all cases.
Kaynak
Energy Conversion and ManagementCilt
51Sayı
12Koleksiyonlar
- Makale Koleksiyonu [109]
- Scopus İndeksli Yayınlar Koleksiyonu [2695]
- WoS İndeksli Yayınlar Koleksiyonu [2986]
İlgili Öğeler
Başlık, yazar, küratör ve konuya göre gösterilen ilgili öğeler.
-
Investigation of irreversibilities in the compression process for alternative refrigerants in a vapor compression refrigeration cycle
Kılıçarslan, Ali; Müller, Norbert (2008)Irreversibility analyses during compression process are presented for some refrigerants namely, R290, R134a, R12, R22, and R152a in a vapor compression refrigeration cycle. The effects of evaporator temperature, condenser ... -
Comparison of superheating effect of water as a refrigerant with the other refrigerants
Kılıçarslan, Ali; Kurtbaş, İrfan (2011)The performance comparison of water as a refrigerant (R718) with some refrigerants including R717, R290, R134a, and R152a is presented for a vapor compression refrigeration cycle. A computer program simulating the vapor ... -
Irreversibility analysis of a compression refrigeration cycle using natural refrigerants for a sustainable future
Kılıçarslan, Ali (2012)Irreversibility analyses of R290, R717, R718 and R744 are carried out in a compression refrigeration cycle. The effects of evaporator temperature, condenser temperature and isentropic efficiency on the irreversibility of ...